The D600 GC (60 Hz)diesel generator sets were developed to meet your needs in a standby application. Producing reliable power of 600 ekW at 60 Hz, meeting ISO 8528-5 transient response requirements and built to accept 100 % rated load in one step. Our D600 GC generator sets meet EPA Stationary Emergency (Tier 2) certified emissions requirements.
Generator Set Specifications | |
---|---|
Maximum Rating | 600 ekW |
Minimum Rating | 600 ekW |
Emissions/Fuel Strategy | EPA Stationary Emergency |
Voltage | 480 to 600 Volts |
Frequency | 60 Hz |
Speed | 1800 rpm |
Duty Cycle | Standby |
Engine Specifications | |
---|---|
Engine Model | Cat® C18 In-line 6, 4-cycle Diesel |
Bore | 5.7 in / 145 mm |
Stroke | 7.2 in / 183 mm |
Displacement | 1106 in³ / 18.1 l |
Compression Ratio | 14.5:1 |
Aspiration | Turbocharged Air-to-Air Aftercooled |
Fuel System | MEUI |
Governor Type | ADEM™A4 |
Generator Set Dimensions | |
---|---|
Length - Maximum | 196.1 in / 4980 mm |
Width - Maximum | 73.4 in / 1865 mm |
Height - Minimum | 79.1 in / 2009 mm |
Height - Maximum | 100.9 in / 2563 mm |
Dry Weight - Genset (minimum) | 8959.6 lb / 4064 kg |
Dry Weight - Genset (maximum) | 11647 lb / 5283 kg |
We'll do our best to get back to you as soon as possible.