XQP60

Width
44.1 in / 1120 mm
Height
70 in / 1776.5 mm
Length
103 in / 2610 mm

This XQP60 generator set provide low fuel consumption performance. With a robust, rental or mobile-ready construction, the product line is designed to be easily transported around project sites safely and efficiently. Heavy-duty bases with integrated fork lift pockets allow the unit to be dragged and lifted with ease, while Clipsal or CEE socket options are available on select models to reduce installation time and provide trouble-free power distribution.

Generator Set
Rating Prime 60 kVA
Frequency 50/60 Hz
Voltage 127 - 480 V
Engine
Engine Cat C4.4
Fuel Diesel
Dimensions
Width 44.1 in / 1120 mm
Height 70 in / 1776.5 mm
Length 103 in / 2610 mm
Weight - With Lube Oil and Coolant 3781 lb / 1715 kg
Fuel Consumption EU Stage IIIA
100% Load 50Hz 4.4 gal/hr / 16.5 l/hr
100% Load 60Hz 5 gal/hr / 18.8 l/hr
75% Load 50Hz 3.3 gal/hr / 12.4 l/hr
75% Load 60Hz 3.8 gal/hr / 14.3 l/hr
50% Load 50Hz 2.2 gal/hr / 8.3 l/hr
50% Load 60Hz 2.6 gal/hr / 9.8 l/hr
Noise rating (with enclosure) EU Stage IIIA
Sound Power @ 1 meters (3 feet) @ 75% of rating (50Hz) 73.3 dB(A)
Sound Power @ 1 meters (3 feet) @ 75% of rating (60Hz) 76.4 dB(A)

Standard Equipment

  • CAT C4.4 Diesel Engine
    • Turbocharged
  • Generator
    • LC1514P Frame
  • Air Filter
    • Cyclonic/paper with dust cup and service indicator
  • Cat Connect remote monitoring
    • Provides package monitoring and management
  • Cooling System
    • Package mounted radiator with vertical air discharge. Filled from factory
  • Charging / Starting System
    • 12V heavy duty starting motor and charging alternator c/w battery isolator
  • Fuel System
    • 24 hour dual wall fuel tank with 3 way directional valve for external supply
  • Control Panel
    • Digital XQCP set mounted controller
  • Distribution
    • Single, robust enclosure for controls and distribution c/w 4 pole circuit breaker and safety cut off
  • Structure
    • Heavy Duty steel base frame with integral fuel tank. Fork lift pockets. Dragging bars. Lifting frame and 4 point lift. base frame is wider than enclosure to protect generator set during transportation.
  • Enclosure
    • Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
  • Exhaust
    • Integrated spark arresting silencer
  • Lube Oil
    • On engine primary and secondary oil filters. Filled from factory
  • General
    • Factory tested and inspected
Contact Us
x

We're here to help

We'll do our best to get back to you as soon as possible.