C3.3 | DE55 GC

Bore
4.1 in / 105 mm
Stroke
5 in / 127 mm
Displacement
201.4 in³ / 3.3 l

Producing reliable power of 50 ekW at 60 Hz, our DE55 GC diesel generator set is designed to meet ISO 8528-5 transient response requirements.

Generator Set Specifications
Frequency 60 Hz
Maximum Rating 50 ekW
Emissions/Fuel Strategy Non Regulated
Voltage 220 to 480 Volts
Minimum Rating 50 ekW
Speed 1800 rpm
Duty Cycle Standby
Engine Specifications
Engine Model Cat® C3.3, In-line 3, 4-cycle diesel
Bore 4.1 in / 105 mm
Stroke 5 in / 127 mm
Displacement 201.4 in³ / 3.3 l
Compression Ratio 17.25:1
Aspiration Turbocharged
Fuel System Inline
Governor Type Mechanical
Generator Set Dimensions
Length - Maximum 76.6 in / 1945 mm
Width - Maximum 34.3 in / 870 mm
Height - Maximum 48.7 in / 1238 mm
Dry Weight - Genset (maximum) 2114 lb / 959 kg

Standard Equipment

  • Engine
    • C3.3, Inline 3 cylinder, 4 stroke diesel
  • Genset Control
    • GCCP 1.1
  • Governor
    • Mechanical governor
  • Alternator
    • A Frame standard alternator
  • Fuel Storage
    • Single wall 8 hour fuel tank
  • Enclosure
    • Cat GC enclosure
  • Air, Cooling & Exhaust
    • Enclosure silencer
  • General
    • Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment

  • Certification
    • Australia, CIS, Gulf Certification
    • Certificate of Conformance
  • Alternator Requirements
    • Space heater
  • Auxiliary Supply Voltage
    • 120V
  • Fuel Storage
    • Dual wall 8 hour fuel tank
    • Low fuel level shutdown
    • Single wall tank with containment
    • Low fuel level alarm
    • High fuel level alarm
  • Genset Control
    • Battery charger
    • Volt free contacts for genset running
    • Volt free contacts for common alarm
    • Emergency stop with key
    • Earth leakage
    • USB to RS485 Communications device
    • Earth fault
    • Panel mounted audible alarm
    • Battery
    • Standby Pack (Smart Jacket water heater, Battery charger)
    • Coolant heater
    • Low coolant level shutdown
  • Circuit breaker
    • 3 Pole Circuit breaker 63A
    • 3 Pole Circuit breaker 80A
    • 3 Pole Circuit breaker 100A
    • 3 Pole Circuit breaker 125A
    • 3 Pole Circuit breaker 160A
    • 3 Pole Circuit breaker 200A
    • 4 Pole Circuit breaker 63A
    • 4 Pole Circuit breaker 80A
    • 4 Pole Circuit breaker 100A
    • 4 Pole Circuit breaker 125A
    • 4 Pole Circuit breaker 160A
    • 4 Pole Circuit breaker 200A
    • Circuit breaker padlock
    • Neutral earth link
    • Overload via alarm switch on breaker
  • Testing & Packaging
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8PF
Contact Us